TYPE CL3 CABLES – Type CL3 and CL2 general-use cables comply with a 70,000 Btu/h (20.5 kW) vertical-tray flame test. The cable one of the following tests:
1) the test method described as the UL Flame Exposure (smoke measurements are not applicable) in the Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables, UL 1685, to cable that is surface marked or designated by a marker tape as ″CL3 ″ or ″CL2 ″.
2) the test method described as the FT4/IEEE 1202 Type of Flame Exposure (smoke measurements are not applicable) in the Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables, UL 1685.
Soft Skin Standard Fire Resistant Cables for general use in fire detection, fire alarm, voice alarm, and emergency lighting circuits. For example: ★ hotels ★ theaters and cinemas ★ museums ★ hospitals ★ shopping centers ★ skyscrapers ★ offices ★ schools ★ Airports★ underground and tunnel ★ railway station ★ computer center ★ alarm system ★ traffic control system ★ fire fighting system
Voltage Rating:300V
Temperature limits: -20°C to +105°C
Minimum Bending Radius: 10~15 times cable outer diameter
Should not be installed at temperatures below 0°C or above+40°C
For more information, please consult members of the lilutong wire and cable sales team